High Voltage 110kV Armoured Electrical Cable 1 Core CU/XLPE/PVC
Application
The cables refer to power cables used for transmitting 100kV, mainly for power transmission and distribution. Its voltage level ranges are commonly used for long-distance power transmission and voltage level conversion in substations.
Construction
Description
Specification
| 
			 Parameter category  | 
			
			 Parameter item  | 
			
			 parameter values  | 
		
| 
			 configuration parameter  | 
			
			 electric conductor  | 
			
			 Material: copper core (cross-section range: 630~1600mm²)  | 
		
| 
			 External diameter of conductor  | 
			
			 30.0~56.5mm (The larger the section, the increasing the outer diameter)  | 
		|
| 
			 insulating course  | 
			
			 Material: Cross-linked polyethylene (XLPE), thickness of 16.5±0.5mm  | 
		|
| 
			 Conductor shielding layer  | 
			
			 Thickness of 1.2mm (semi-conductive material)  | 
		|
| 
			 insulation screen  | 
			
			 Thickness of 1.0mm (semi-conductive material)  | 
		|
| 
			 metallic sheath  | 
			
			 Wrinkle aluminum sheath (2.0±0.2mm) (double galvanized steel strip, 0.5~0.8mm)  | 
		|
| 
			 oversheath  | 
			
			 Material: flame retardant polyvinyl chloride (PVC) or polyethylene (PE), thickness of 4.5±0.2mm  | 
		|
| 
			 Electrical parameters  | 
			
			 20℃ conductor DC resistance  | 
			
			 0.0754~0.009 Ω / km (the larger the section, the lower the resistance)  | 
		
| 
			 90℃ conductor AC resistance  | 
			
			 0.097~0.0142Ω/km  | 
		|
| 
			 capacity value  | 
			
			 134-282 p F/m (increased with increasing cross-section)  | 
		|
| 
			 Power frequency pressure test  | 
			
			 64 / 110kV (factory test)  | 
		|
| 
			 Local discharge performance  | 
			
			 At 5pC(1.5U₀ under-voltage)  | 
		|
| 
			 Mechanical and laying parameters  | 
			
			 minimum bending radius  | 
			
			 12 x cable outer diameter (armor layer requirement)  | 
		
| 
			 Allow working temperature  | 
			
			 Long-term: 90℃, short circuit (within 5 seconds): 250℃  | 
		|
| 
			 Laying ambient temperature  | 
			
			 ≥0℃  | 
		|
| 
			 Vehicle flow reference  | 
			
			 Flow rate in single return air  | 
			
			 Section 630mm²: 1010A; section 1600mm²: 1690A (ambient temperature 40℃, soil thermal resistance 1.0m · ℃ / W)  | 
		
| 
			 Load flow rate of directly buried laying  | 
			
			 Section 630mm²: about 800A; section 1600mm²: about 1300A (buried depth 1m, ground temperature 35℃)  |